Ammonia Absorption Refrigeration Plant & Single Effect Lithium Bromide Absorption Refrigeration Plants for Chilled Water Application

Ammonia Absorption Refrigeration Plant Single Effect Lithium Bromide Absorption Chiller
Application Range : Application Range
Operating Temp. Range: +5 to -60oC : Operating Temp Range: +7 & above
Driving Heat Source Temp Range : 85oC & above. : Driving Heat Source Temp Range: 85oC & above
Cooling water Temp: 35oC or below. : Cooling water Temp: 35oC or below

-------------------

Construction : : Construction :
Refrigerant - Ammonia (NH3) : Refrigerant - Water
Absorbent - Water : Absorbent - Lithium Bromide (LiBr)

-------------------

Material of Construction : Material of Construction
Plates - Carbon Steel : Plates - Carbon Steel
Tubes - Carbon Steel : Tubes - Copper Nickel Tubes
All welded construction : Tubes to tubesheet are expanded joint rest is welded construction
Operating System pressure is above atmosphere upto (-30oC) : System is under vacuum

-------------------

Functioning : Functioning 
- Fully automatic continuous Modulation : - Fully automatic continuous Modulation
- Part load efficiency is good : - Part load efficiency is good

-------------------

Maintenance & Spares : Maintenance & Spares
- No Maintenance : - Vacuum maintenance is critical functions and system life 
- Tubes are carbon steel & solution pumps are standard centrifugal pumps. : - Copper Nickel tubes & Hermetic pumps are very costly 
: - Copper Nickel tubes need replacement periodically & hence repair cost is high.

-------------------

Life - Long life of 25 years or more

:

Life - Entire equipment life is not more than 15 years.

-------------------

Corrosion : Corrosion is high
Corrosion is negligible : Highly susceptible to corrosion and therefore life can be limited if vacuum is not maintained properly. Expanded tube-to-tubesheet joints have tendency to leak periodically.

-------------------

Due to low corrosion repairs maintenance costs are very low

:

Due to corrosion tube repairs and replacement is frequent. All tubes are Copper or Copper Nickle Tubes. Therefore tube replacement is very costly.

-------------------

Due to pressurized system; No special care is needed

:

Due to vacuum System ; special care is needed otherwise plant stops frequently. Also due to thousand of expanded tube to tubesheet joints, the vacuum loss is frequent with passage of time. Fault finding is very time consuming.

-------------------

Chilled water application : : Chilled water application :
Chilled water temperature  : Chilled water temperature
7oC outlet : 7oC outlet
12oC return : 12oC return
Cooling water temperature : 30oC : Cooling water temperature: 30oC
Driving Heat Sources temperature 85oC to 140oC : Driving Heat Source temperature 85oC to 140oC
C.O.P.: 0.6 to 0.65 : C.O.P.: 0.6 to 0.65
Conclusion : Hot water driven AARP is a more reliable Absorption System than Single Effect LiBr Chiller for production of chilled water using hot water of temperatures less than 100oC.

 